趋势七
提升配电能力将成为智算中心新的诉求

在智算中心,随着机柜功率密度的提升以及AI机柜的集群化部署,IT机房的配电面临额定容量偏小的挑战。比如,过去一个300 kW的配电模块可以支持几十台甚至是上百台机柜。而如今,同样配电模块的电量甚至无法支持一个低配置的NVIDIA DGX SuperPOD AI集群(单排358 kW的10个机柜,每机柜36 kW)。配电模块规格太小,使用多个配电模块不仅浪费IT空间,也变得不切实际。与单个大容量配电模块相比,多个配电模块还会增加成本。回归配电的本质,提高配电容量的主要手段就是增大电流。
施耐德电气观点:
在设计时应选择规格足够高的配电模块,实现弹性部署,从而适应未来的配电需求,以至少支持一整排集群为准。
比如,在额定电压下,800 A的配电模块是目前适用于所有三种配电类型(PDU,RPP和母线)的标准容量尺寸,可提供576 千瓦(降容后为461 千瓦)。对于末端配电可以使用小母线,从而避免了定制大于63 A额定电流的机柜PDU。在空间允许的情况下,可以使用多个标准化的机柜PDU作为过渡。